SPACE / PLANNING

Zoning, Clean Level, Layout

Cell culture processing facilities in the field of regenerative medicine are required to comply with cleanliness classifications based on GCTP ministerial ordinances and ISO 14644.

We consistently design and propose standard equipment layouts that meet the requirements for each class, including Grade A to D zone configurations, from the planning stage.

● Zoning

4-1.jpg

We adopt zone configurations tailored to the grade.

A configuration that ensures positive pressure, differential pressure, and air change rates in the center, while accommodating the flow of people, goods, and materials on the outside.

Each class ensures independence through anterooms, pass-throughs, and differential pressure control.

*Compliance Standards: GCTP Ministerial Ordinance, ISO 14644, Three Principles of GMP

● Clean Level

Grade

A

B

C

D

Area Classification

Critical Operation Area

Inside BSC/Isolator

Direct Support Area

Culture Room

Other Support Areas

Preparation Room / Main Work Area

Other support areas

Sterilizer/Machine room

Japanese Pharmacopoeia

A

B

C

D

ISO 14644-1

Class 5

Class 7

Class 8

-

Non-working hours

3,520

3,520

352,000

3,520,000

During operation

3,520

352,000

3,520,000

​-

【Grade A】

​

Area Classification: Critical Operation Area BSC

Inside Isolator

 

Japanese Pharmacopoeia: A

 

ISO 14644-1: Class 5

 

At Rest: 3,520

 

In Operation: 3,520

【Grade B】


Area Classification: Direct Support Area

Culture Room

​

Japanese Pharmacopoeia: B


ISO 14644-1: Class 7

​

At Rest: 3,520


In Operation: 352,000

*Unit: Maximum allowable particle count (particles/m³) / Particle size 0.5 μm or larger

[Grade C]


Area classification: Other support areas

Preparation room / Main work area

 

Japanese Pharmacopoeia: C

​

ISO 14644-1: Class 8

​

At rest: 352,000


In operation: 3,520,000

*Compliance Standards: The 15th Edition of the Japanese Pharmacopoeia / ISO 14644-1

[Grade D]


Area Classification: Other support areas

Sterilizer/Machine room

​

Japanese Pharmacopoeia: D


ISO 14644-1: -

​

At rest: 3,520,000


In operation: -

4-2.jpg

Keep heat, moisture, and noise outside the culture room

The cell manipulation area (A) is inside the culture room (B), and the culture room is inside the support area (C, D).

We maintain a nested structure where the center has higher cleanliness, preventing direct access from outside air or corridors.

Nesting sterile spaces

Separate equipment with high environmental impact, such as sterilizers, freezers, and refrigerators, into zones C and D.

Do not disturb the temperature, humidity, airflow, or particle control within the culture room, and do not transmit vibrations during long-term operation.

Separate the flow lines for people, materials, and waste.

Separate the flow lines for cell manipulation from those for pretreatment, sterilization, and waste disposal using an anteroom/pass-through to suppress contamination risk at the source.

Separate the work flow lines for the biosafety cabinet unit and the centrifuge, even within the same culture room.

● Principles of Layout